Fct. Text Description and settings
3.03 ZERO SET Zero calibration
Note:
Carry out only at “0” flow and with completely filled
measuring tube!
Precautionar
y query
CALIB. NO
Press
key to return to Fct. 3.03 “ZERO SET”.
CALIB. YES Press
key to start calibration.
Duration approx. 25 seconds, current flowrate
displayed in the selected unit (see Fct. 1.04 “DISP. FLOW”).
A “WARNING” sign appears when flowrate “>
0
“;
acknowledge by pressing
key.
STORE NO (do not store new zero value)
STORE YES (store new zero value)
Press
key to return to Fct. 3.03 “ZERO SET”.
3.04 ENTRY CODE Entry code required to enter setting mode?
NO (= entry with only)
YES (= entry with and Code 1: → → → ↵ ↵ ↵ ↑ ↑ ↑ )
Press
to return to Fct. 3.04 “ENTRY CODE”.
3.05 USER UNIT Set any required unit for flowrate and counting
TEXT VOL. Set text for required flowrate unit (max. 5 characters)
Factory-set: “Liter” or “MGal”.
Characters assi
gnable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character).
Press
key to transfer to subfunction “FACT. VOL.
FACT. VOL. Set conversion factor (F
M
) for volume
Factory set “1.00000” for “Liter” or “2.64172E-4” for “US MGal”
(exponent notation, here: 1
x
10
3
or 2.64172
x
10
-4
).
Factor F
M
= volume per 1m
3
.
Setting range 1.00000 E-9 to 9.99999 E+9 (= 10
-9
to 10
+9
)
Press
key to transfer to subfunction “TEXT TIME”.
TEXT TIME Set text for required time unit (max. 3 characters)
Factory-set: “hr” or “day”:
Characters assignable to each place:
A-Z, a-z, 0-9, or “ – “ (= blank character).
Press
key to transfer to subfunction “FACT. TIME”
FACT. TIME Set conversion factor (F
T
) for time
Factory-set: “3.60000 E+3” for “hour” or “8.64000 E+4” for “day”
(exponent notation, here: 3.6
x
10
3
or 8.64
x
10
-4
).
Set factor F
T
in seconds.
Setting range
1.00000 E-9 to 9.99999 E+9 (= 10
-9
to 10
+9
)
Press
key to return to Fct. 3.05 “USER UNIT”.
3.06 APPLICAT. Set overload point for A/D converter
FLOW STEADY (150% of Q
100%
) PULSATING (1000% of Q
100%
)
Press key
to return to
Fct. 3.06 “APPLICAT.“,
with installed option
“empty pipe“
,
change to subfunction
“EMPTY PIPE“.
EMPTY PIPE Switch on “empty pipe” identifier option?
(appears only when this option is installed)
YES NO
Select with key
.
Press
key to return to
Fct. 3.06 “APPLICAT.“.
3.07 HARDWARE Assign outputs and inputs to terminals B1 and B2
TERM.B1 Terminal B1
PULSOUTP. STATUSOUTP. CONTROLINP.
Select with key
.
Press key
to transfer to subfunction
“TERM. B2”.
TERM.B2 Terminal B2
STATUSOUTP. CONTROLINP.
Select with key
.
Press key
to return to
Fct. 3.07 “HARDWARE”.