ADAM-6022 Dual Loop PID Controller User’s Manual
Output Channel Configuration Page : For output channel configuration, there are two analog output channel in ADAM-6022. The output channel 0 is used
PID Loop Configuration ADAM-6022 is designed as a stand alone PID controller. We offer a very convenient software tool for user to configure the PID
PV, MV Alarm Status PID Setting Bottom (go to PID setting page) PID Tuning Bottom (go to PID tuning page) After finishing the setup work in conf
PV Range Low PV low limit value Low Pass Filter Low Pass Filter set value Low Pass Filter Calculation : MV Feedback = Reading MV x Filter Value + Pre
MV E-Stop Value Setting MV frozen value while PID being emerged shutdown For PID parameter tuning, please refer the PID tuning page. In this page,
Appendix A Command Set ASCII command Command Description Remarks $aaArr Set the integration time for the module !01: OK ?01: error $aaAccrr Se
module. $aaM Return the module name from the specified module!016022: OK ?01: error $aaRST Reset password to “00000000” !01: OK ?01: error $aaRcchhh
?01: error @aaMASK Read subnet mask !01mmmmmmmm ?01: error @aaGW Read default gateway !01mmmmmmmm ?01: error @aaDEVNAME Read device name !01ssssss
Warning Message : The ADAM-6022 is recommended to be used in general purposed air conditioning application. When using this product in applications
Appendix B Communication Specification Serial communication Baud rate: 19200 bps Data bits: 8 Parity: 0 Stop bit: 1 Flow control: non
PID Parameters Table: PID Parameter for Loop 0 : Modbus Register Code Read/WriteDecimalPlace Descriptions 41001 Open/Close Mode Read / Write 0 Enab
41035 MV & FB RH (Range low) Read / Write 3 MV Engineering Value Range high MV RL must < MV RL 41037 PV-1 engineering data Read Only 3 PV So
(msec) for PV-1 41083 Control loop period setting (msec)for PV-2 Read / Write 0 <=0 : Loop empty >0 : Loop controlling 41085 Control loop per
41121 PV-2 Alarm L limit Read / Write 3 PV-2 Alarm Low Limit Value (>PV-2 RL & PV-2 Alarm LL) 41123 PV-2 Alarm Dead Band % Read / Write 3 PV
41265 Process value_1 bare data Read Only 3 Loop 0 PV_0 value。 41267 Process value_2 bare data Read Only 3 Loop 0 PV_1 value 41269 Manipulator value
41305 PV_1 Filter value Read / Write 3 1st order filter value for PV source 1 0<(PV_1 Filter value/1000)<1.0 41307 PV_2 Filter value Read / Wri
action setting Write keep PID open 1: setting the previous MV output as initial value and keeping PID Close 2: PID open, using MV initial value
41407 PID Direct/Reverse Read / Write 0 0:Direct Mode 1:Reverse Mode 41409 SV-1 High Limit Read/ Write 3 SV-1 High Limit value 41411 SV-1 Low Limit R
ADAM-6022 dual loop PID Controller Introduction Function The ADAM-6022 dual loop PID controller is a PC-based stand alone controller. It was
Wiring & Installation The ADAM-6022 is a 2 loop PID controller. There are three analog input, one analog output, one digital input and one digita
Application Wiring Fig. 7-2 Analog Input/Output Wiring Diagram Fig. 7-3 Digital Input Wiring Diagram
Fig. 7-4 Digital Output Wiring Diagram Open Collector
Jumper Setting The Backup SRAM jumper default setting is “Disable”. Please set the jumper in “Enable” when using ADAM-6022. I : Current Signal
Operation Interface Open the ADAM Ethernet IO Utility Software, the software tool will auto-scan the ADAM Ethernet module through the network. Clicki
Input Channel Configuration Page : In ADAM-6022 input channel configuration page, user can enable the input channel, select the input signal type and